zone apply command
Syntax
- zone apply keyword <range>
-
Create or modify zone conditions. This command is used to apply conditions to the volume represented by zones — i.e., body forces or fluid/thermal sources. For application of boundary conditions on surfaces represented by zone faces, see the
zone face apply
command. The user must specify the condition type, the numerical value, optional modifiers, and an optionalrange
over which the condition is to be applied. If no range is specified, then the command applies to the entire model. Removal of zone conditions is done with a separate command — seezone apply-remove
.After the supplied condition’s value (f or v), an optional modifier keyword can be used to modulate the supplied value. The position of the modifier in the command is marked [zoneapplyoptions]; the valid modifier keywords are found in the Keyword Block section at the end of this topic. The modifiers can be used to vary the value of the applied condition in both time and space.
All values are considered to be per unit volume.
Apply conditions that conflict with currently existing ones will overwrite them.
- force v [zoneapplyoptions]
All components (x, y, and z) of the body force per unit volume applied to a zone.
- force-x f [zoneapplyoptions]
The x-component of the body force per unit volume applied to a zone.
- force-y f [zoneapplyoptions]
The y-component of the body force per unit volume applied to a zone.
- force-z f [zoneapplyoptions]
The z-component of the body force per unit volume applied to a zone.
- source f [zoneapplyoptions]
A heat-generating source, f, is applied as a volume source of the specified strength (e.g., in W/m3 ) in each zone in the specified range. When a new source is applied to a zone with an existing source, the new source strength replaces the existing source strength.
Decay of the heat source over time can be represented by applying one of the available modifiers.
Note this keyword is only available for the thermal model option.
- well f [zoneapplyoptions]
A volume rate of flow, f (i.e., fluid volume per zone volume per unit time), is specified for each zone in the specified range (f > 0 for inflow).
Note: A fluid flow model must exist for this command to work.
Keyword Block
The following keywords may be used to modify the base value supplied. force
, force-x
, force-y
, force-z
, source
and well
.
- fish s
Specify a multiplier that is a FISH function named s. The return value of this FISH function is multiplied by the base value (including gradient) over all zones included in this apply condition. So a return value of 1.0 will apply the base value provided, and a return value of 0.0 will effectively remove it. This function will be called every step.
If the apply condition requires a vector value, this function should also return a vector.
- fish-local s
Specify a multiplier that is a FISH function named s, which is applied separately to each individual zone affected by this apply condition. This function must take two arguments, the first of which will be a pointer to the specific zone. The second argument is not used. This allows an apply condition to vary over time as well as space. The returned value of this FISH function is multiplied by the base value (including gradient) on the specific zone supplied. So a return value of 1.0 will apply the base value provided, and a return value of 0.0 will effectively remove it. This function will be called every step for every zone included in the apply condition.
If the apply condition requires a vector value, this function should also return a vector.
- gradient v <origin v >
Applies a gradient in space to the scalar-value provided. The position used in this calculation is the zone centroid. Another way of assigning a linear gradient is with the vary modifier.
- servo keyword ...
Use a servo tied to the mechanical convergence ratio to control the magnitude of the applied condition. This can be used to maintain, gradually ramp up, or gradually reduce apply conditions while maintaining a quasi-static response. By default the multiplier will start at 0.001, and will gradually increase to 1.0 as the convergence ratio falls below 2e-3, and decrease if it rises above 1e-2. The following keywords are available to control the servo response:
- latency i
The minimum number of steps that must pass since the last servo adjustment before the next one occurs. This can keep the servo from overcontrolling in the initial response to an adjustment. The default value is 1.
- lower-bound f
Set the lower mechanical convergence ratio value. If the current ratio falls below this value, the current multiplier will be multiplied by the lower-multiplier. The default value is 2e-3.
- lower-multiplier f
If the current ratio falls below the lower-bound, the value is multiplied by this. The default value is 0.975.
- minimum f
The minimum value the current multiplier is allowed to become. The default value is 0.001.
- ramp
Sets the servo into ramp mode. This means that the current multiplier is not allowed to go down, the value will only increase. This is useful to gradually increase an applied condition to it’s full value. See also the reduce keyword.
- ratio keyword
Which mechanical convergence ratio is compared against lower-bound and upper-bound. By default this is the current value assigned by the
zone ratio
command (which is average by default. See thezone ratio
command for definitions. The available keywords are:
- average
Use the average mechanical force ratio.
- maximum
Use the maximum mechanical force ratio.
- local
Use the local mechanical force ratio.
- reduce
Sets the servo into reduce mode. In this mode the starting value of the current multiplier is 1.0, and the minimum value is set to 0.0. When the current ratio falls below lower-bound the current multiplier is reduced by the upper-multiplier. The current multiplier is never increased. This is useful to gradually decrease an applied condition to zero.
- table s <time keyword>
Specify a value multiplier that is a table (named s). By default, the x-value of the table is the step number. The returned value of this table is multiplied by the base value (including gradient) over all zones included in this apply condition. So a return value of 1.0 will apply the base value provided, and a return value of 0.0 will effectively remove it. The table lookup will be performed every step. The time scale for the x-axis can also be selected by giving the time keyword followed by one of the following options:
- step
- creep
- dynamic
- fluid
- mechanical
- thermal
- vary v
Apply a linear variation to the scalar-value provided. The position used in this calculation is the zone centroid. Another way of assigning a linear gradient is with the gradient modifier.
zone.apply can be used
Was this helpful? ... | PFC 6.0 © 2019, Itasca | Updated: Nov 19, 2021 |